Loading...
Chapter 13 RS-232C function of K200S MASTER-K
13-26
[ Data configuration of status data ]
à Byte
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Not used
Error
code
Not used
CPU
mode
Key /
Flash
Not used
O/S
version
CPU
type
- CPU type
CPU type Code
K200S A (K3P-07AS) h3A
K200S B (K3P-07BS) h3B
K200S B (K3P-07CS) h3C
K300S A (K4P-15AS) h33
K300S B (K4P-07AS) h37
K1000S (K7P-30AS) h32
- O/S version : (Use only lower 8 bits)
Example) O/S version 1.2
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
0 0 0 1 0 0 1 0
- Key / Flash
bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
Not used Not used
0 : Flash memory is mounted
1: Flash memory is not mounted
0 : Mode key is on local mode
1: Mode key is on remote mode
- CPU mode (Use only lower 4 bits) : Turn on one bit according to the operation
mode of master CPU.
bit 3 bit 2 bit 1 bit 0
DEBUG PAUSE STOP RUN
- Error code : Refer the chapter 12.5 Error code list