Chapter 3 General specifications MASTER-K
3-1
3 General specifications
The following table shows the general specifications of MASTER-K series.
No Item Specifications Remark
1
Operating ambient
temperature
0 ~ 55 (32 ~ 131 °F)
2
Storage ambient
temperature
-25 ~ 70 (-13 ~ 158 °F)
3
Operating ambient
humidity
5 ~ 95%RH, non-condensing
4
Storage ambient
humidity
5 ~ 95%RH, non-condensing
Occasional vibration
Frequency Acceleration Amplitude Sweep count
10f<57 Hz - 0.075 mm
57 f150 Hz 9.8 (1G) -
10 times in each
direction for X, Y, Z
Continuos vibration
Frequency Acceleration Amplitude
10f<57 Hz - 0.035 mm
5 Vibration resistance
57f150 Hz 4.9 (0.5G) -
10 times in each
direction for X, Y, Z
IEC 1131-2
6 Shock resistance
Maximum shock acceleration: 147 (15G)
Duration time :11 ms (3 times in each of X, Y and Z directions)
Pulse wave: half sine wave pulse
IEC 1131-2
Square wave
impulse noise
±1,500 V
LGIS ’ s
specification
Electrostatic
discharge
Voltage :4 kV(contact discharge)
IEC 1131-2
IEC 801-2
Radiated electro-
magnetic field
27 ~ 500 MHz, 10 V/m
IEC 1131-2
IEC 801-2
Severity
Level
All power
modules
Digital I/O
( Ue 24 V)
Digital I/O (Ue<24 V)
Analog I/O
Communication I/O
7 Noise immunity
Fast transient
burst noise
Voltage 2 kV 1 kV 0.25 kV
IEC 1131-2
IEC 801-4
8 Atmosphere Free of corrosive gases
9 Altitude for use Up to 2,000m ( 6,560ft )
10 Pollution degree 2
11 Cooling method Self-cooling
Remark
1. IEC (International Electrotechnical Commission) : The international civilian organization which
produces standards for electrical and electronics industry.
2. Pollution degree : It indicates a standard of operation ambient pollution level. The pollution
degree 2 means the condition in which normally, only non-conductive pollution occurs.
Occasionally, however, a temporary conductivity caused by condensation shall be expected.