EasyManua.ls Logo

LSIS Master-K K1000S - Page 35

LSIS Master-K K1000S
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 CPU modules MASTER-K
4-12
1) Parameter setting
K200S K300S K1000S
Priority Type Period Priority Type Period Priority Type Period
0
1
2
:
:
7
TDI0
TDI2
TDI5
:
:
INT7
10ms
25ms
100ms
0
1
2
:
:
:
13
TDI0
TDI2
TDI5
INT7
10ms
25ms
100ms
0
1
2
:
:
:
:
29
TDI0
TDI2
TDI5
INT15
10ms
25ms
100ms
Remark
Period is the interval of time driven interrupt occurring. It is variable from 10 ms to 60,000 ms
(60ms) by 10 ms.
Remark
Interrupt processing during momentary power failure:
If process-driven interrupts occur during a momentary power failure (power failure less than 20
ms), they are executed after the power is recovered. If a time-driven interrupt occurs two or
more times during momentary power failure, it is executes only once after power is recovered.
During momentary power failure, the CPU keep measuring time and the period of momentary
power failure is included in the period of TDI.

Table of Contents