Chapter 7 Input/Output Specifications
7-9
7.2.3 XBC-DR20E 12 point DC24V input (Source/Sink type)
Model
Specification
Main unit
XBC-DR20E
Input point
12 point
Insulation method
Photo coupler insulation
Rated input voltage
DC24V
Rated input current
About 4 (Contact point 0~3: about 7 )
Operation voltage range
DC20.4~28.8V (within ripple rate 5%)
On voltage / On current
DC19V or higher / 3 or higher
Off voltage / Off current
DC6V or lower / 1 or lower
Input resistance
About 5.6 (P00~P07: about 2.7 )
Response
time
Off On
1/3/5/10/20/70/100 (set by I/O parameter) default: 3
On Off
Insulation pressure
AC560Vrms / 3 cycle (altitude 2000m)
Insulation resistance
10 or more by MegOhmMeter
Common method
12 point / COM
Proper cable size
0.3
Operation indicator
LED On When Input On
External connection
method
24 point terminal block connector (M3 X 6 screw)
Weight
450g
Circuit configuration
No.
Contact
No.
Contact
Type
TB1
RX
TB2
485+
TB3
TX
TB4
485-
TB5
SG
TB6
00
TB7
01
TB8
02
TB9
03
TB10
04
TB11
05
TB12
06
TB13
07
TB14
08
TB15
09
TB16
0A
TB17
0B
TB18
NC
TB19
NC
TB20
NC
TB21
NC
TB22
NC
TB23
NC
TB24
COM
DC24V
Internal
circuit
R
0B
0
TB6
COM
DC5V
Photo coupler
Terminal block no.
TB17
TB24
LED
R
TB2
TB4
TB6
TB8
TB10
TB12
TB14
TB16
TB18
TB20
TB22
TB24
TB1
TB3
TB5
TB7
TB9
TB11
TB13
TB15
TB17
TB19
TB21
TB23
www.behaotomasyon.com