Chapter 14 Maintenance
111
Chapter 14 Maintenance
Be sure to perform daily and periodic maintenance and inspection in order to maintain the PLC in the best
conditions.
14.1 Maintenance and Inspection
The I/O module mainly consist of semiconductor devices and its service life is semi-permanent. However,
periodic inspection is requested for ambient environment may cause damage to the devices. When inspecting
one or two times per six months, check the following items.
Check Items
Judgment
Corrective Actions
Change rate of input voltage
Within change rate of input
voltage
(Less than 15% to +20% )
Hold it with the allowable range.
Power supply for input/output
Input/Output specification of
each module
Hold it with the allowable range of each module.
Ambient
environment
Temperature
0 ~ + 55
Adjust the operating temperature and humidity with the
defined range.
Humidity
5 ~ 95%RH
Vibration
No vibration
Use vibration resisting rubber or the vibration prevention
method.
Play of modules
No play allowed
Securely enrage the hook.
Connecting conditions of
terminal screws
No loose allowed
Retighten terminal screws.
Spare parts
Check the number of
Spare parts and their
Store conditions
Cover the shortage and improve the conditions.
14.2 Daily Inspection
The following table shows the inspection and items which are to be checked daily.
Check Items
Check Points
Judgment
Corrective
Actions
Connection conditions of
base
Check the screws.
Screws should not be loose.
Retighten
Screws.
Connection conditions of
Input/Output module
Check the connecting screws
Check module cover.
Screws should not be loose.
Retighten
Screws.
Connecting conditions of
terminal block or extension
cable
Check for loose mounting screws.
Screws should not be loose.
Retighten
Screws.
Check the distance between solderless
terminals.
Proper clearance should be provided.
Correct.
Connecting of expansion cable.
Connector should not be loose.
Correct.
LED
indicator
PWR LED
Check that the LED is On.
On(Off indicates an error)
See chapter 4.
Run LED
Check that the LED is On during Run.
On (flickering or On indicates an
error)
See chapter 4.
ERR LED
Check that the LED is Off during Run.
Flickering indicates an error
See chapter 4.
Input LED
Check that the LED turns On and Off.
On when input is On,
Off when input is off.
See chapter 4.
Output LED
Check that the LED turns On and Off
On when output is On,
Off when output is off
See chapter 4.