Chapter 4 CPU Specifications
4.1 Performance Specifications
The following table shows the general specifications of the XGB compact type CPU
(XBC-Dx10/14/20/30E).
Items
Specifications (“E” type)
Remark
XBC-DR10E
XBC-DR14E
XBC-DR20E
XBC-DR30E
XBC-DN10E XBC-DN14E XBC-DN20E XBC-DN30E
XBC-DP10E XBC-DP14E XBC-DP20E XBC-DP30E
Program control method Reiterative operation, fixed cycle operation, constant scan
-
I/O control method
Scan synchronous batch processing method (Refresh method),
Directed by program instruction
Program language Ladder Diagram, Instruction List
Number of
instructions
Basic 28
Application 677
Processing speed
(Basic instruction)
0.24 /Step
Program capacity 4 k steps
Max. I/O points
14 point
Main + 1 option
18 point
Main + 1 option
28 point
Main + 2 options
38 point
Main + 2 options
Data area
P P0000 ~ P127F (2,048 point)
M M0000 ~ M255F (4,096 point)
K K00000 ~ K2559F (Special area: K2600~2559F) (40,960 point)
L L00000 ~ L1279F (20,480 point)
F F000 ~ F255F (4,096 point)
T
100ms, 10ms, 1ms : T000 ~ T255 (256 point)
(Adjustable by parameter setting)
C C000 ~ C255 (256 point)
S S00.00 ~ S127.99
D D0000 ~ D5119 (5120 word)
Word
U
U00.00 ~ U07.31
(Analog data refresh area: 256 word, analog data refresh area)
Z Z000~Z127 (128 Word)
Total program 128
-
Initial task 1
Cyclic task Max. 8
I/O task Max. 4
Internal device task Max. 8
Operation mode RUN, STOP, DEBUG
Self-diagnosis function Detects errors of scan time, memory, I/O
Program port RS-232C (Loader)
Back-up method Latch area setting in basic parameter
www.behaotomasyon.com