EasyManua.ls Logo

LSIS XBC-DR14E - 7.6 Combined Digital I;O module Input Specification

LSIS XBC-DR14E
384 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7 Input/Output Specifications
7-69
7.6 Combined Digital I/O module Input Specification
7.6.1 8 point DC24V input (Source/Sink type)
Model
Specification
DC input module
XBE-DR16A
Input point
8 point
Insulation method
Photo coupler insulation
Rated input voltage
DC24V
Rated input current
About 4
Operation voltage range
DC20.4~28.8V (within ripple rate 5%)
On Voltage/Current
DC19V or higher / 3 or higher
Off Voltage/Current
DC6V or less / 1 or less
Input resistance
About 5.6
Response
time
Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
On Off
Insulation pressure
AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance
10 or more by Megohmmeter
Common method
8 point / COM
Proper cable size
Stranded cable 0.3~0.75 (External diameter 2.8 or less)
Current consumption
280 (When all inputs and outputs are on)
Operation indicator
LED on when input on
External connection
method
9 pin terminal block connector
Weight
81g
Circuit configuration
No.
Contact
Type
TB1
0
TB2
1
TB3
2
TB4
3
TB5
4
TB6
5
TB7
6
TB8
7
TB9
COM
DC24V
Internal
circuit
R
7
0
TB1
COM
DC5V
Photo coupler
Terminal
block no.
TB8
TB9
LED
R
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
www.behaotomasyon.com
www.behaotomasyon.com

Table of Contents