Chapter 10 DC Input Option Board
10 - 14
(4) Parameter setup
(a) Action command
Type
Device status information (based on slot 9, ch0)
Ref.
CH0
Information
Enable counter
U9.0.0
0: disable, 1: enable
BIT
Enable internal preset
U9.0.1
0: disable, 1: enable
BIT
Count inc/dec flag
U9.0.3
0: INC, 1: DEC
BIT
Latch counter enable
U9.0.6
0: disable, 1: enable
BIT
Pulse input mode
U9.5
0: 1-phase 1-input
1: 1-phase 2-input
2: 2-phase 2 multiplication
INT
Internal preset setting value
U9.6
-2,147,483,648 ~ 2,147,483,647
DINT
(b) Monitor area
Type
Device status information (based on slot 9, ch0)
Ref.
CH0
Information
Carry flag
U9.1.0
0: disable, 1: enable
BIT
Borrow flag
U9.1.1
0: disable, 1: enable
BIT
Current counter value
U9.2
-2,147,483,648 ~ 2,147,483,647
DINT
Error code
U9.4
Indicates error code
INT
10.4.2 Error code
Describes on error of option board high-speed counter
Describes error code
Error
code
(Dec.)
Error contents
Ref.
21
Pulse input type range setting error
22
CH1(3) RUN request while CH0(2) 2-phase RUN
* CH1(3) is not available when CH0(2) operate as 2-phase mode
25
Internal preset value exceeded counter range
Note
If more than two errors occur, the latest error code is saved and previous error code is removed.