Chapter 12 Memory Module
12-9
(3) Reading program in PLC to memory module
(a) When password of program in PLC is not set
1) When no password is set in the memory module
- Reads program from PLC
2) When password is set in the memory module
- After reading, it clears password of the memory module
(b) When password of program in PLC is set
1) When no password is set in the memory module
- Writing is not executed
2) When password is set in the memory module
- When PLC password is same as that of the memory module, writing is executed.
- When PLC password is not same as that of the memory module, writing is not executed.
(4) When LED flickers
Operating mode changes while being connected to PADT or
PLC
Connected to PADT while mode switch is “1”
PLC program upload is prohibited
You execute reading when password is set in PLC
(when password is not same as that of memory module)
Connected to PADT while mode switch is “3”
You execute writing the memory module when PLC mode is
RUN
Connected to the different type of PLC with the type set in the
memory module
You executes writing when PLC password is not same as that of
memory module
-. Memory module can cancel PLC password and read/write but can‟t set, delete and change the
password.
-. Do not run PLC while external memory module is connected to.