Please, install protection circuit on the exterior of PLC to protect 
   the whole control system from any error in external power or PLC 
  module. Any abnormal output or operation may cause serious problem 
  in safety of the whole system.   
-  Install applicable protection unit on the  exterior of PLC to  protect 
the system from physical damage such as emergent stop switch, 
protection  circuit,  the  upper/lowest  limit  switch,  forward/reverse 
operation interlock circuit, etc. 
-  If any system error (watch-dog timer error, module installation error, 
etc.) is detected during CPU operation in PLC, the whole output is 
designed to be turned off and stopped for system safety. However, 
in case CPU error if caused on output device itself such as relay or 
TR  can  not  be  detected, the  output  may  be  kept  on,  which  may 
cause serious problems. Thus, you are recommended to install an 
addition circuit to monitor the output status. 
 
 Never connect the overload than rated to the output module nor 
  allow the output circuit to have a short circuit, which may cause a 
  fire. 
 
 Never let the external power of the output circuit be designed to 
    be On earlier than PLC power, which may cause abnormal output or 
operation. 
 
 In  case  of  data  exchange  between  computer  or  other  external 
equipment and PLC through communication or any operation of 
PLC (e.g. operation mode change), please install interlock in the 
sequence program to protect the system from any error. If not, it 
may cause abnormal output or operation.