Chapter 5 Program Configuration and Operation Method
5- 36
(2) Data latch area operation
(a) The method to delete the latched data is as below.
- latch 1, latch 2 clear operation by XG5000
- write by Program (initialization program recommended)
- write0‟ FILL from XG5000 monitor mode.
For keep or reset (clear) operation of latch area data according to PLC operation, please refer to the
below table.
No.
Classification
Detailed operation
Latch 1
Latch 2
1
Power change
Off/On
Keep
Keep
2
Reset by XG5000
Overall reset
Reset
Keep
3
Program write (online)
-
Keep
Keep
4
Data broken
SRAM broken by battery error
Reset
Reset
Data broken by other reason
Reset
Reset
5
XG5000 online
Clear Latch 1
Reset
Keep
Clear Latch 2
Reset
Reset
(b) Latch 1 area is cleared byOnline-Reset PLC- “Overall reset.