bNin
Binary input
function
none
none: none
stop: control stop
Hand: switching into manual
working
sp2: switching SP1 into SP2
rSat: erasing of timer alarm
Psta: program start
Pnst: jump to the next
segment
PHld: stopping to count the
set point in the program
outp – Output parameters
out1
Function of
output 1
y
off: without function
Y: control signal - heating
or control signal „open”
for analog valve
Y0p: control signal for the
stepper control – opening
YCl: control signal for the
stepper control - closing
Cool: control signal - cooling
or control signal „close”
for analog valve
AHi: upper absolute alarm
Alo: lower absolute alarm
dwHi: upper relative alarm
dwlo: lower relative alarm
dwin: inner relative alarm
dwou: outer relative alarm
aLtr: timer alarm
retr: retransmission
eu1: auxiliary output for the
program-following control
eu2: auxiliary output for the
program-following control
aLfl: alarm in case of sensor
failure or exceeding the
measuring range
o1.ty Output type 1 4-20 2) rely: relay output
ssr: voltage output 0/5 V
4-20: continuous current
output 4 – 20 mA
0-20: continuous current
output 0 – 20 mA
0-10: continuous voltage output
0 – 10 V