2-9
Note:
The inverter can be started via the frequency reference input with preset
direction of rotation.
FS > 0.5 Hz → START
FS < 0.25 Hz → STOP
In addition to the adaption of the FSINA input to the jumper rail, the device
software offers adaption options with the K
EYPAD or via the interface.
The parameter 04-FSSEL (frequency reference selector) determines the
origin of the frequency reference (see table). Also see parameter
description.
FSINA(F) digital frequency reference input
04-FSSEL Function
0 Analog input active, adaption via jumper rail J1...J6
1, 2 No function
3 FSIN as frequency input 0 to 1 kHz active
4 FSIN as frequency input 0 to 10 kHz active
5 FSIN as PWM input 20 to 100% active
6 FSIN as PWM input 0 to 100% active
7 FSIN not active, reference via KP100 (CTRL-menu)
8 Reference preset via interface
9 to 16 Reference presetting see Chapter 6 Page 6-4
17 to 22 Correction of the analog reference via S1IND/S2IND
(MOP function) active
23 Inverted analog input: 10 V => FMIN, 0 V => FMAX