2.4.6 Signal outputs
S1OUT collective error message (Relay output)
The operating contact Kl. 41/42 is closed, if there is a inverter malfunction.
The contact opens again, if the fault has been rectified or the mains have
been disconnected.
The error message is acknowledged by pressing the stop/return key for at
least 3 secs or by a signal to one of the digital inputs (see Parameter 75-
OPT1 Page 6-20).
S2OUT stand-by (Relay output)
The make contact Kl. 44/45 is closed, as soon as the pre-charging is
completed after power on and there is no fault. The make contact
Kl. 44/45 is opened, as soon as a fault arises or the mains is switched off.
Programming:
Both outputs can be set to one of 10 different functions with the KEYPAD or
via the interface. The function description relates to the following factory
settings:
Parameter 62-S1OUT = 10
Parameter 63-S2OUT = 1
Further information see parameter description, Chapter 6.