6-5
6.2 Actual values
09-BARG Bar graph display [Decimal]
The following parameters can be depicted in the bar graph display.
09-BARG Function
STAT Depiction as bit model, see Fig. 6-3
12-F Output frequency as analog bar, Des. < F >
13-V Output voltage, Des. < V > (Factory setting)
14-IS Apparent current as analog bar, Des. < I >
15-IW Effective current as analog bar, Des. < I >
SIN Depiction as bit model, see Fig. 6-3
09-BARG = 11-STAT
A -> generating current
B -> current limiting value reached
I
S
> 110% I
N
C -> 12-F > 25-FF5
D -> reference reached
Fig. 6-3
09-BARG = 66-SIN
A -> S2OUT active
B -> S1OUT active
C -> S2IND active
D -> S1IND active
10-G Scaled frequency
Displays the actual output frequency 12-F multiplied with the factor from
parameter 86-KG, no decimal fractions or physical units being displayed.
(10_G) = (12_F) ∗ (86_KG)
12-F Output frequency [Hz]
Displays the actual output frequency. After error shut-down, the actual
value existing before shut down is saved (Hold-Function).
VAL
Hz
A
BCD