6-18
62-S1OUT Programmable control output S1OUT [Decimal]
63-S2OUT Programmable control output S2OUT [Decimal]
62-S1OUT Function
63-S2OUT
0,9 Without function, outputs S_OUT = 0
1 active, as soon as inverter on mains and no error existing
2 active, as long as motor excited
3 active, as long as counter-clockwise speed > 0 or DC hold active
4 active, as long as clockwise speed > 0 or DC hold active
5 active, as long as rotary field frequency 12-F = 0
6 active as soon as reference reached
7 active, if rotary field frequency 12-F > 25-FF5
8 active, if apparent current 14-IS > 110%,
59-TRIP current limit reached
10 active, after an error shut-down
Factory setting: 62-S1OUT ->10, 63-S2OUT -> 1
6.8 Program functions
67-FST Filter time constants [Decimal]
Determines the filter time constants for analog reference input FSIN.
(see also 04-FSSEL). Temporal performance as PT1-member
(deceleration pass).
67-FST Function
00 ms
1 8.2 ms
2 24.6 ms, factory setting
3 57.4 ms
4 123 ms