6-19
69-KOUTA Factor for analog output 61-SOUTA [Decimal]
This parameter enables the scaling of the analog output SOUTA.
When an analog signal is issued, the voltage is multiplied by the factor
69-KOUTA in accordance with the programming and limited to 15 V.
71-PROG Special programs [Decimal]
With 71-PROG, special programs can be activated. Possible special
programs at present:
71-PROG Function
0 No special program active
1 Reset to factory setting "A" e.g. Europe
(according to design 71-PROG = 0)
2 changed significance of the control terminals
STR = 0 -> clockwise, STL = 1 -> START
STR = 1 -> counter-clockwise, STL = 0 -> STOP
4 as 1, however factory setting "B" e.g. USA
72-STRT Starting options [Decimal]
72-STRT Function
0 No starting option active, factory setting
1 Autostart after mains on with STL or STR bypassed
2 Synchronisation to running motor
3 Autostart and synchronisation
4 Rotation direction block: counter-clockwise
rotation blocked
5 Rotation direction block and autostart
6 Rotation direction block and synchronisation
7 Autostart, synchronisation, rotation direction block