5-4
5.3 Inverter-type dependent and nationally-related parameters
Abbrev. Page Name Unit WE- WE- Inverter type
AB
44-VN1 6-10 Voltage rated point 1 V 230 230 VF1205M...VF1207M
44-VN1 6-10 Voltage rated point 1 V 400 460 VF1404M...VF1410M
47-VN2 6-11 Voltage rated point 2 V 230 230 VF1203M...VF1207M
47-VN2 6-11 Voltage rated point 2 V 400 460 VF1404M...VF1410M
50-IN 6-13 Motor rated current, A 4.5 4.5 VF1205M
56-ILIM 6-16 Current limit, A 6.2 6.2 VF1207M
59-TRIP 6-16 I x t monitoring A 3.5 3.4 VF1404M
A 5.4 4.8 VF1406M
A 7.1 6.3 VF1408M
A 8.9 7.7 VF1410M
53-KIXR 6-14 Corr. factor I∗R comp. - 7 7 VF1205M
53-KIXR 6-14 Corr. factor I∗R comp. - 4 4 VF1207M
53-KIXR 6-14 Corr. factor I∗R comp. - 18 18 VF1404M
53-KIXR 6-14 Corr. factor I∗R comp. - 12 12 VF1406M
53-KIXR 6-14 Corr. factor I∗R comp. - 8 8 VF1408M
53-KIXR 6-14 Corr. factor I∗R comp. - 8 8 VF1410M
54-KSC 6-14 Corr. factor slip comp. % 6.7 6.7 VF1205M
54-KSC 6-14 Corr. factor slip comp. % 6 6 VF1207M
54-KSC 6-14 Corr. factor slip comp. % 6 6 VF1404M
54-KSC 6-14 Corr. factor slip comp. % 5.3 5.3 VF1406M
54-KSC 6-14 Corr. factor slip comp. % 5.3 5.3 VF1408M, VF1410M
Solely nationally related parameters
22-FMAX1 6-7 Maximum frequency 1 Hz 50 60
29-FMAX2 6-7 Maximum frequency 2 Hz 50 60
43-FN1 6-10 Frequency rated point 1 Hz 50 60
46-FN2 6-11 Frequency rated point 2 Hz 50 60
52-NN 6-13 Rated speed UPM 1390 1710
Factory setting (FS):
The factory setting can be adjusted with the KEYPAD in the PARA menu. To
this end parameter 71-PROG must be set to 1 (WE-A e.g. for Europe) or
71-PROG to 4 (WE-B e.g. for USA).