6-7
6.3 Frequencies
20-FF2-1 1st fixed frequency FF2 [Hz]
Parameter of the 1st data set.
As reference can be selected via S1IND = 1, S2IND = 0 and S3IND = 0
21-FMIN1 Minimum frequency for analog reference input [Hz]
Parameter of the 1st data set. Reference input FSIN = 0 (2) V or
0 (4) mA corresponds to an output frequency of FMIN.
22-FMAX1 Maximum frequency for analog reference input [Hz]
Parameter of the 1st data set. Reference input FSIN = 10 V or 20 mA
corresponds to an output frequency of FMAX.
23-FF3 Fixed frequency FF3 [Hz]
As reference can be selected via S1IND = 0, S2IND = 1 and S3IND = 0
24-FF4 Fixed frequency FF4 [Hz]
As reference can be selected via S1IND = 1, S2IND = 1 and S3IND = 0
25-FF5 Fixed frequency FF5 [Hz]
Frequency thresholds for programmable outputs S1OUT, S2OUT and
S3OUT. (also see 62-S1OUT 63-S2OUT, 64-S3OUT)
As reference can be selected via S1IND = 0, S2IND = 0 and S3IND = 1
26-FF6 Fixed frequency FF6 [Hz]
Frequency threshold for data set changeover at 31-KSEL = 1
As reference can be selected via S1IND = 1, S2IND = 0 and S3IND = 1
27-FF2-2 2nd fixed frequency FF2 [Hz]
Parameter of the 2nd data set
As reference can be selected via S1IND = 1, S2IND = 0 and S3IND = 0
28-FMIN2 Minimum frequency for analog reference input [Hz]
Parameter of the 2nd data set (see also 21-FMIN1).
29-FMAX2 Maximum frequency for analog reference input [Hz]
Parameter of the 2nd data set (see also 22-FMAX1).
30-FF7 Fixed frequency 7 [Hz]
As reference can be selected via S1IND = 0, S2IND = 1 and S3IND = 1