6-4
04-FSSEL = 7
FSIN is not active. When starting the MOP function in the CTRL-
menu of the KEYPADS, 04-FSSEL = 7 is set automatically, and reset to
04-FSSEL = 0 on quitting.
04-FSSEL = 8
FSIN input and KEYPAD input are not active. Reference can only be
entered externally via interface.
04-FSSEL = 9...16
FSIN input and KEYPAD input are not active. Function see Fig. S.6-2.
04-FSSEL = 17
1)
FSIN input active (base reference). The reference can be continuously
raised with S1IND and continuously lowered with S2IND (Reference
offset with MOP function).
04-FSSEL = 18
1)
Has same function as 04-FSSEL = 17 with following supplement:
With simultaneous activation of S1IND and S2IND, the reference is
reset to the base reference (Reference offset = 0).
04-FSSEL = 19
1)
Has the same function as 04-FSSEL = 17 with following supplement:
With preset reference offset and mains off, this offset is saved until it is
modified or reset via S1IND and S2IND.
04-FSSEL = 20
1)
Has the same function as 04-FSSEL = 18 and 19
04-FSSEL = 21
1)
Has the same function as 04-FSSEL = 17 with following supplement:
When the inverter is stopped, the reference is reset to the base
reference (Reference offset = 0).
04-FSSEL = 22
1)
Has the same function as 04-FSSEL = 18 and 21
04-FSSEL = 23
1)
The FSIN input functions as inverted analog input.
10 V = FMIN 0V = FMAX
1) see description of the MOP function with S1IND/S2IND in
Chapter 2.4.5