32-RACC1 Start-up ramp [Hz/s]
Parameter of the 1st data set, see Fig. 6-4.
33-RDEC1 Deceleration ramp [Hz/s]
Parameter of the 1st data set, see Fig. 6-4.
34-RACC2 Start-up ramp [Hz/s]
Parameter of the 2nd data set, see Fig. 6-4.
35-RDEC2 Deceleration ramp [Hz/s]
Parameter of the 2nd data set, see Fig. 6-4.
36-RSTOP Stop ramp [Hz/s]
With activated stop ramp (36-RSTOP > 0) the inverter after setting of the
control inputs STR and STL to 0, carries out a deceleration ramp with a
gradient of 36-RSTOP, see Fig. 6-5. Subsequent maintenance of the
DC current is possible with 38-THTDC > 0. With 36-RSTOP = 0 the motor
comes to a halt by itself, if STL and STR are set to 0.
DS1 = Data set 1
DS2 = Data set 2
Fig. 6-4
Fig. 6-5
0
f
t
0
f
t
RACC2
RACC1
RDEC2
RDEC1
RACC1
RSTOP
RDEC1
DS1 DS2 DS1