6-22
94-MAXF Absolute maximum frequency [Hz]
Is the maximum frequency which is produced by the inverter. The
parameter is applied with frequency reference formation, current limit
value regulation, slip compensation and synchronisation to running motor.
Setting 0 signifies: The limiting of MAXF is switched off. Then only the
limitation from 22-FMAX1 or 29-FMAX2 is still active.
95-ERR1 Error 1 [Decimal-0.1h]
Stores the last error message.
Representation:
Error No.
-
Error time
see table 0.1 h = 6 Min. / max. 1.5 h
is reset after each error message
Possible error messages:
No. Significance
1-time Error in computer component
2-time Low voltage (no entry in 95-ERR1 ÷ 98-ERR4)
3-time Excess current, short circuit or earthed after mains on
4-time Excess voltage
5-time I * t Motor
6-time I * t Inverter
7-time Excess temperature motor
8-time Excess temperature inverter
9-time Error in EEPROM
Acknowledge error by pressing stop/return-key for at least 3 sec. or with
digital signal as described under 75-OPT1.