Physical Inputs and Outputs (AI’s, AO’s, BI’s & AO’s)
Use JP2 jumper to choose
between BO7 or AO1
Default
value
Tags
Minimum
range value
Maximum
range value
Inactive_Text Active_Text
BO_1 Based on MSV127 config
Off
Status
Off On
BO_2 Based on MSV127 config
On
Status
Off On
BO_3 Based on MSV127 config
Off
Status
Off On
BO_4 Based on MSV127 config
Off
Status
Off On
BO_5 Based on MSV127 config
Off
Status
Off On
BO_6 Based on MSV127 config
Off
Status
Off On
BO_7 Based on MSV127 config
Off
Status
Off On
AO_ECM Based on MSV127 config
0%
Status
0% 100%
AO_2 Based on MSV127 config
0%
Status
0% 100%
AO_3 Based on MSV127 config
0%
Status
0% 100%
AO_4 Based on MSV127 config
0%
Status
0% 100%
AI_1 Analog input 1 Status
Based on AI1_cfg object MSV46
AI_2 Analog input 2 Status
Based on AI2_cfg object MSV47
AI_3 Analog input 3 Status
Based on AI3_cfg object MSV48
AI_4 Analog input 4 Status
RoomT Room temperature
N/A
Status
32°F (0°C) 122°F (50°C)
RoomRH Room humidity
N/A
Status
5% 90%
RoomCO2 Room CO2 Status
0 PPM 2000 PPM
Motion Motion detection
Off
Status
Off Active
Please note that objects tagged as:
• Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
• User: represent properties or objects that are typically manipulated by users of the controller
• Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
• Cmd: represent objects that can be controlled directly by other BACnet external process
Please note: Object description for all the BO’s and AO’s are automatically generated by the configuration of MSV127 and will refresh automatically based on BV4 = On