Installation
I/O Wiring & Sequence
MSV127 – HP DEH
HP DEH: Sets for a 1 on/off fan, 2 on/off heatpump, 1
on/off dehumidification, 1 reversing valve stages
HEATPUMP unit
Notes:
- BO6 is an occupancy output that follows the main occupancy
- BO6 is an on/off dehumidification output that follows
dehumidification demand
- AI’s can be configured for various options as per MSV2, 27, 28,
66 & 67
Add 24VAC transformer when the power
is not supplied by the equipment
18
19
20
21
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1COM
24VAC
(R)
BO1
BO2
BO3
BO4
BO5
BO6
AO1/BO7
AO2
AO3
COM
AI1
AI2
A+
B-
AO4
COM
AI3
AI4
MS/TP
AO1
BO7
JP2
EOL
NONE
JP3
Heatpump
(2 compressors / 1 dehum)
G
C
R
Y1
Y2
O
OCC
Service
Dehum
SAT
www.lynxspring.com