Cooling and heating stages
Application Note
Binary Output
(Binary outputs staging): There is a fixed 3 min delay before the first stage of heating or cooling will start. There is a 1 min delay for each stage afterward. See
demand curves on each sequence in this guide.
Change Over
(Heating/Cooling Change Over): There is a fixed 3 min delay before the first stage of heating or cooling will start when changing over from heating or cooling
for both Binary and Analog outputs.
Analog Output
(Analog outputs staging): There is a fixed 1 min delay before the analog outputs of heating or cooling will start. Staging will depend on the [AV-59] calculated
effective SAT against the [AV-16] Supply air Temp. This is calculated internally by the PID. See demand curves on each sequence in this guide.