Binary Values
Please note that objects tagged as:
Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
User: represent properties or objects that are typically manipulated by users of the controller
Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
Cmd: represent objects that can be controlled directly by other BACnet external process
www.lynxspring.com
Object
Instance
RTU
Object name
Description
Tags
Default
value
Inactive_Text Active_Text
BV2
OVRSTAT Occupancy override status Status Normal Normal Overrid
BV3
Mot_Det Motion detection Status Moving None Moving
BV4
AutogenDesc Autogenerate I/O descriptions Cfg Off Off On
BV5
Occ_Sch System occupancy schedule Status --- Off On
BV7
Freeze_Status Freeze condition status Status --- Normal Active
BV8
Free_CL_Status Free cooling authorization status Status --- No Yes
BV21
EnthalpyAuth Enthalpy Authorize Status --- No Yes