7 Troubleshooting
MAGNETEK HPV1000 AC Elevator Drive Technical Manual 47
EF1
Ext Flt S1 Alarm
External fault at Logic Input 1 on
terminal S1.
An external device has tripped an alarm function.
Remove the cause of the external fault and reset the fault.
Wiring is incorrect.
Ensure the signal lines have been connected properly to the terminals
assigned for external fault detection.
Reconnect the signal line.
Incorrect Logic Input settings.
Check for incorrect setting of Logic Inputs in the C2 sub-menu for external
faults.
EF2
Ext Flt S2 Alarm
External fault at Logic Input 2 on
terminal S2.
EF3
Ext Flt 3
Ext Flt S3 Alarm
External fault at Logic Input 3 on
terminal S3.
EF4
Ext Flt 4
Ext Flt S4 Alarm
External fault at Logic Input 4 on
terminal S4.
EF5
Ext Flt 5
Ext Flt S5 Alarm
External fault at Logic Input 5 on
terminal S5.
EF6
Ext Flt 6
Ext Flt S6 Alarm
External fault at Logic Input 6 on
terminal S6.
EF7
Ext Flt 7
Ext Flt S7 Alarm
External fault at Logic Input 7 on
terminal S7.
EF8
Ext Flt 8
Ext Flt S8 Alarm
External fault at Logic Input 8 on
terminal S8.
End1
(auto-tune)
Excessive V/f Setting (detected only
during Rotational Auto-Tuning, and
displayed after Auto-Tuning is complete).
The torque reference exceeded 20% during Auto-Tuning, or the results from
Auto-Tuning the no-load current exceeded 80%.
Before Auto-Tuning the drive, verify the information written on the motor
nameplate and enter the data in to the A5 menu and verify in the U9 menu.
Enter parameters and repeat Auto-Tuning.
End2
(auto-tune)
Motor Iron-Core Saturation Coefficient
(detected only during Rotational
Auto-Tuning and displayed after
Auto-Tuning is complete).
Motor data entered during Auto-Tuning was incorrect.
Make sure the data entered match the information written on the motor
nameplate.
Restart Auto-Tuning and enter the correct information.
Results from Auto-Tuning are outside the parameter setting range, assigning
the Saturation Comp 1 and Saturation Comp 2 parameters a temporary value.
Check and correct faulty motor wiring.
End3
(auto-tune)
Rated Current Setting Alarm (displayed
after Auto-Tuning is complete)
The correct current rating printed on the nameplate was not entered into
Rated Current in the U9 sub-menu during Auto-Tune.
Check the setting of parameter Rated Current in the U9 sub-menu.
Check the motor data and repeat Auto-Tuning.
End4
(auto-tune)
Adjusted Slip Calculation Error
The slip that was calculated is outside the allowable range.
Make sure the data entered for Auto-Tuning in the U9 sub-menu is correct.
Execute the “Standard Tuning” in the U9 sub-menu for a rotational
auto-tune. If a rotational auto-tune cannot be done, try “Tune-No Rotate2.”
End5
(auto-tune)
Resistance Tuning Error
The resistance value that was calculated is outside the allowable range.
Double-check the data that was entered for the Auto-Tuning process.
Check the motor and motor cable connection for faults.
End6
(auto-tune)
Leakage Inductance Alarm
Control Method (U8) setting error.
Check the setting of Control Method (U8).
Check the control mode and repeat Auto-Tuning.
The leakage inductance value that was calculated is outside the allowable
range.
Double-check the data that was entered for the auto-tune process in Leak
Inductance (A5).
Fault Code/Name Description Causes and Solutions