27
The nine arithmetic functions are:
Flow Compensation Linear
Flow Compensation Square Root
Flow Compensation Approximate
Btu Flow
• Traditional Multiply and Divide
Average
Summer
Fourth Order Polynomial
Simple HTG Compensate Level
ST_REV: The revision level of the static data associated
with the function block. The revision value will increment
each time a static parameter value in the block is changed.
TAG_DESC: The user description of the intended applica-
tion of the block.
STRATEGY: The strategy field can be used to identify
grouping of blocks. This data is not checked or processed by
the block.
ALERT_KEY: The identification number of the plant unit.
This information may be used in the host for sorting
alarms, etc.
MODE_BLK: The actual, target, permitted, ad normal
modes of the block.
• Target: The mode to go to
Actual: The mode the “block is currently in
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
BLOCK_ERR: This parameter reflects the error status
associated with the hardware or software components associ-
ated with a block. It is a bit string so that multiple errors
may be shown.
PV: The primary analog value for use in executing the
function, or a process value associate with it.
OUT: The analog output value and status.
PRE_OUT: Displays what would be the OUT value if the
mode was Autoor lower.
PV_SCALE: Associated with the PV.
OUT_RANGE: The high and low scale values, engineering
units code, and number of digits to the right of the decimal
point associated with OUT.