ECODRIVE DKC01.1/DKC11.1 Drive Controllers
DOK-ECODRV-ASE-02VRS**-WAR1-EN-P • 07.96 Description of Diagnostic Letters F... and E... 2-1
2 Description of Diagnostic Letters F... and E...
2.1 Error Diagnostic Messages
UL Motor Type not Reported
Description:
The settings for current regulation, velocity command, and position loop
are stored in the feedback of the motor. After powering up, the drive
compares the motor type stored in the parameters with the connected
motor type. If the two do not match, the drive remains at this state.
By pressing the S1 button, the drive overwrites its stored parameters with
the control loop parameters from the motor feedback.
Cause:
Motor was exchanged.
The parameter "P-0-4036, contacted motor type" from which the motor
type is selected would be loaded..
Remedy:
Command "C700 Basic Load” or press the S1 button.
PL Default Value of the Parameter Load
Description:
After the exchange of the product (EPROMs), if the parameters have
been changed in regards to the old product, the drive displays "PL". By
pressing the S1 button on the drive or through starting of the „command
load basic parameter", all the parameters will be erased and restored with
the default values.
Cause:
Product was exchanged and the number of parameters of the new
product has changed in regards to the old.
Remedy:
Press the S1 button on the drive controller and all the parameters will be
erased and restored with default values
WARNING
⇒ With this procedure all parameters and process
blocks will be overwritten.