22 TORKEL 900-SERIES ZP-CS01E CS033663DE
5 MAKING A TEST
2] Press "Yes"
3] Disconnect the cables in reverse order that
they were connected.
WARNING
Do not connect a discharged battery to a
battery that has not been discharged. The
batteries must be charged to the same
potential (voltage) before they are con-
nected together.
For viewing results and report see section "5.7 View-
ing results and reporting" on page 26.
5.3 Test at constant power
TORKEL can be used to conduct a discharge test at
constant power instead of constant current. All proce-
dures are the same except that you must set TORKEL
differently before starting – you set the power instead
of the current.
Preparations
Follow the safety precautions set forth in section "2.2
Safety instructions" on page 8 and the prepara-
tions for testing in section "5.1 Preparations for test-
ing" on page 20.
Configuring TORKEL for constant
power
1] Calculate the current at the end of the test
(divide the power by the voltage).
2] Then make sure that the total current does
not exceed 2999 A and that the TORKEL and
TXL units can load with the required current
throughout the test.
Select "Test Method"
1] Press "Constant P"
2] Set the desired Power by pressing the nu-
meric field and make the settings for power
using the On-screen keyboard.
3] Make settings for warning and stop limits,
see section "Warning and stop limit param-
eters" on page 14.
Tip
You can change the settings for power and
limits at any time in "TEST".
Starting the test
4] Press
The power value (kW) will be displayed and
the control knob lamp will blink.
Pausing the test
1] Press
2] Restart by pressing
Note Any TXL Loads connected to TORKEL must be
restarted manually.