CS033663DE ZP-CS01E TORKEL 900-SERIES
23
5 MAKING A TEST
Ending the test
WARNING
Do not disconnect any cables until the test
is completed and stopped
1] Press
2] Press "Yes"
3] Disconnect the cables in reverse order as
described in section "Connecting the current
cables to the battery" on page 20
WARNING
Do not connect a discharged battery to a
battery that has not been discharged. The
batteries must be charged to the same
potential (voltage) before they are con-
nected together.
For viewing results and report see section "5.7 View-
ing results and reporting" on page 26.
5.4 Test at constant
resistance
TORKEL can be used to conduct a discharge test at
constant resistance instead of constant current. All
procedures are the same except that you must set
TORKEL differently before starting – you set the resist-
ance instead of the current.
Preparations
Follow the safety precautions set forth in section "2.2
Safety instructions" on page 8 and the prepara-
tions for testing in section "5.1 Preparations for test-
ing" on page 20.
Select "Test Method"
1] Press "Constant R"
2] Set the desired Resistance by pressing the nu-
meric field and make the settings for resist-
ance using the On-screen keyboard.
3] Make settings for warning and stop limits,
see section "Warning and stop limit param-
eters" on page 14.
Tip
You can change the settings for resistance
and limits at any time in "TEST".
Starting the test
4] Press
The resistance value (Ohm) will be displayed
and the control knob lamp will blink.
Pausing the test
1] Press
2] Restart by pressing
Note Any TXL Loads connected to TORKEL must be
restarted manually.
Ending the test
WARNING
Do not disconnect any cables until the test
is completed and stopped
1] Press