MI 3000 EasiPLUS IT supply systems
66
Trip-out time
Complete measurement range corresponds to EN61557-6 requirements. Specified
accuracies are valid for complete operating range.
General (non-delayed) RCDs
Measuring range (ms) Resolution (ms) Accuracy
0 300 (½I
N
, I
N
)
1
0 150 (2I
N
)
1
0 40 (5I
N
)
1
3 ms
Selective (time-delayed) RCDs
Measuring range (ms) Resolution (ms) Accuracy
0 500 (½I
N
, I
N
)
1
0 200 (2I
N
)
1
0 150 (5I
N
)
1
3 ms
Test current ...................................... ½I
N
, I
N
, 2I
N
, 5I
N
5I
N
is not applicable for I
N
100 mA (RCD types AC,A)
2I
N
is not applicable for I
N
500 mA (RCD type AC) or I
N
300 mA (RCD type A)
I
N
is not applicable for I
N
=1000 mA (RCD type AC) or I
N
500 mA (RCD type A)
Trip-out current
Trip-out current (I
N
=10 mA)
Measurement range corresponds to EN61557-6 requirements. Specified accuracies are
valid for complete operating range.
Measuring range I
Resolution I
Accuracy
0.2I
N
1.1I
N
(AC type) 0.05I
N
0.1I
N
0.2I
N
2.2I
N
(A type) 0.05I
N
0.1I
N
Trip-out current (I
N
30 mA)
Measurement range corresponds to EN61557-6 requirements. Specified accuracies are
valid for complete operating range.
Measuring range I
Resolution I
Accuracy
0.2I
N
1.1I
N
(AC type) 0.05I
N
0.1I
N
0.2I
N
1.5I
N
(A type,
N
I
) 30 mA
0.05
I
N
0.1I
N
Trip-out time
Measuring range (ms) Resolution (ms) Accuracy
0 300
1
3 ms
Contact voltage
Measuring range (V) Resolution (V) Accuracy
0.0 9.9
0.1
(-0 % / +15 %) of reading +
2 digits
10.0 99.9
0.1 (-0 % / +15 %) of reading