EasyManuals Logo

METREL EasiPLUS MI 3000 User Manual

METREL EasiPLUS MI 3000
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
MI 3000 EasiPLUS Measurements
41
5.4.2 The fault loop impedance test for RCD protected circuits
The fault loop impedance is measured with a low test current to avoid tripping the RCD.
This function can also be used for fault loop impedance measurement in system
equipped with RCDs which have a rated trip-out current of 10 mA and above.
Prospective fault current (IPFC) is calculated on basis of measured resistance as
follows:
PEL
N
PFC
Z
U
I
Where:
Nominal input voltage U
N
Voltage range
115 V
(100 V
U
L-PE
160 V),
230 V
(160 V U
L-PE
264 V),
For additional information concerning fault loop impedance measurement refer to
Metrel’s handbook Measurements on electric installations in theory and practice.
5.4.2.1 How to perform RCD trip-lock measurement
Step 1 Select the LOOP function with the function selector switch and use the /
keys to select Zsrcd sub-function. The following menu is displayed:
Figure 5.31: Trip-lock function menu
Step 2 Set the following measuring parameters:
Fuse type,
Fuse current rating,
Fuse trip-out time,
Impedance scaling factor (see chapter 4.5.2 Impedance scaling factor
adjustment
).
The complete list of available fuse types can be found in Appendix A.
Step 3 Connect the appropriate test leads to the instrument and follow the
connection diagram shown in figure 5.15 to perform RCD trip-lock
measurement (see chapter 5.3.6 Contact voltage). Use Help function if
necessary.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the METREL EasiPLUS MI 3000 and is the answer not in the manual?

METREL EasiPLUS MI 3000 Specifications

General IconGeneral
BrandMETREL
ModelEasiPLUS MI 3000
CategoryTest Equipment
LanguageEnglish

Related product manuals