EasyManua.ls Logo

Metso ND9200F - Valve travel calibration

Metso ND9200F
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 7 ND92F 70 en
5.5.6 Valve rotation direction, ROT
The application-specific parameter ROT defines the rela-
tionship between position sensor rotation and valve
action.
Once ROT is displayed press the ? key to enter
the edit state and ROT starts to blink.
Now you may select between two values by
pressing the + or - key. The value cC indicates
clockwise rotation for closing the valve and ccC
means counterclockwise to close.
After the desired value is displayed, press the
key ? to conclude the operation.
5.5.7 Valve dead angle, A0
The α
0
setting is made for Metso segment and ball valves.
This setting takes into account the "dead angle" α
0
of the
ball valves. The entire signal range is then used for effec-
tive valve opening 90° - α
0
. Use 0 % as the "dead angle"
for the valves not mentioned in Table 5.
After selecting A0 on the display, press the ?
key to enter the edit state and A0 starts to blink.
The value currently selected appears as a per-
centage (%) on the display.
Modify the parameter value by pressing + or -
keys alternately until the desired value appears
on the display.
Press the ? key to make your selection and
return to the setting state.
5.5.8 Language selection, LANG
Select between three languages EnG, GEr or FrE
using the + and - keys.
To conclude press the ? key when the desired
value is shown on the display.
5.5.9 Low cut-off, low limit, high cut-off,
high limit
ND9200F supports signal cut-off and limiting in both
ends of the operating range. The configuration parame-
ters are; low cut-off, low limit, high cut-off and high limit.
If the input signal is smaller than low cut-off
(TRANSDUCER_BLOCK.FINAL_VALUE_CUTOFF_LO),
the valve will be fully closed.
If the input signal is smaller than low limit
(TRANSDUCER_BLOCK.FINAL_VALUE_RANGE.LO),
the valve stays in the low limit.
If the input signal is greater than high cut-off
(TRANSDUCER_BLOCK.FINAL_VALUE_CUTOFF_HI),
the valve will be fully opened.
If the input signal is greater than high limit
(TRANSDUCER_BLOCK.FINAL_VALUE_RANGE.HIGH),
the valve stays in the high limit.
The cut-off overrides the limit as follows:
NOTE:
Perform valve calibration and tuning always when con-
troller fail action parameter has been changed.
NOTE:
Perform valve calibration and tuning always when ROT
has been changed.
Taulukko 5 Dead angle in percentage
Valve
size
Valve series
MBV
QMBV
1)
MBV
QMBV
2)
D,
P,
C
T5,
QT5
QX-
T5
T25,
QT25
QX-
T25
R,
QR
ER-
SOFT
3)
FL
4)
ZX
mm in Dead angle, %
15 1/2 15
20 3/4 15
25 1 14 - - 25.5 19.5 - - 15 25.5 27 12.5
25/1 1/1 14.5 11
25/2 1/2 8 11
25/3 1/3 8 10
25/4 8
40 1 1/2 12 - - 24.5 12.5 - - 12 16 21 12.5
50 2 10 9 13.5 24.5 12.5 18 8 17 20.5 23 12.5
65 2 1/2 9 - - - - - - 13 - 18
8031081218816.58.598.515.5
100 4 10 8 12 16.5 8.5 16 9 8 7 14.5
125 5 12 - - - - 12 6.5 8 -
150 6 10 8 11.5 16 9 13.5 8 13.5 13
200 8 9 7 8.5 12 6.5 9.5 7 11.5
250 10 9 7 7.5 13.5 9.5 7 10.5
300 12 8 6 6.5 9.5 7.5 6 9.5
350 14 6 6 - 5 9.5
400 16 5 5.5 9.5
(14")
59.5
450 18 6 7.5
(16")
500 20 6 4.5
600 24 5.5 6
650 26 7
700 28 7 6
750 30 6
800 32 -
900 36 5.5
1) Seat supported 2) Trunnion 3) Soft seated R-valve 4) Low Cv Finetrol
Fig. 14 Principle of setting
Fig. 15 Dead angle
100
80
60
40
20
0
0 20 40 60 80 100
α
0
Position
Input signal
low cut-off safety range 2 ± 0.5 %
Basic setting α
0
setting

Table of Contents

Related product manuals