7 ND92F 70 en 23
7.5 Notifications 8 TROUBLE SHOOTING
Mechanical/electrical defects
1. A change in the valve position setpoint will not affect
the position of the actuator
Supply pressure too low
Spool valve sticks
Incorrect configuration parameters
Actuator and/or valve jammed
Signal wires incorrectly connected, no value on
display
Circuit boards are defective
Calibration and tuning has not been carried out
Device is in manual mode
Prestage is defective
Device is in fail-safe mode
2. The actuator goes to the end position with a small
change of input signal
Tubes between controller and actuator are incor-
rect, see Fig. 6
The parameter settings PFA and ROT are incor-
rectly selected.
3. Inaccurate positioning
Spool valve dirty
Too high actuator load
Supply pressure too low
Spool or pressure sensors are defective
Actuator leakage
4. Overshooting or positioning too slow
Change PERF value
Spool valve dirty
Supply air tube too small or supply air filter dirty
Valve sticks
Check leakages in tubes between controller and
actuator
Check leakages in mechanical stop screws
5. Error during valve travel calibration
Valve controller is in MAN mode
Check the coupling alignment with the pointer,
see Fig. 5.
The parameter settings PFA and ROT are incor-
rectly selected
The actuator or valve did not move or was stuck
during calibration
Supply pressure too low
Spool valve dirty
Display message Description
CALIBRATION
SUCCESSFULL
Position calibration
successfully performed.
TEST CANCELLED Off-line test has been
cancelled.
TEST DONE Off-line test has been
successfully performed.
TEST FAILED Off-line test failed. Repeat
the test sequence.
CALIBRATION CANCELLED Calibration has been
cancelled.
PARAMETERS BACKUP
RESTORED
Parameter backup database
has been activated.
PT NOT ACTIVATED (Only with position
transmitter option).
The position transmitter is not
energized.
1PT CAL FAILED 1-point calibration failed.
Check the mounting of the
valve controller. Verify input
parameter (range) value.
Check rotation parameter
(ROT).
TUNE OK Tuning has been
successfully performed.
REDUCED PERFORMANCE
DEACTIVATED
Spool valve measurement
and normal valve control is
recovered.