QUICK START PARAMETERS
Alter the Quick Start Parameters as required to suit installation requirements.
If the Quick Start Guide was used, proceed to .
Refer to TECHNICAL REFERENCE Application Examples for assistance, if required.
P001 OPERATION
Enter the type of RUN mode operation desired.
Select: "level", to display how full the vessel is (from Empty P006) .
"space", to display how Empty the vessel is (from Span P007).
"distance", to display material surface distance from the transducer face.
When "out-of-service" is selected, the transducer is removed from the RUN mode scan
sequence and all Peripherals hold "last known" values/operating status for the
Point Number displayed.
values: 0 = out-of-service
1 = level
2 = space
3 = distance (preset)
P002 MATERIAL
Enter the type of material to be monitored.
If the material presents a flat surface perpendicular to the transducer beam, select liquid.
values: 1 = liquid or flat surface (preset)
2 = solid
P003 MEASUREMENT RESPONSE
Enter how quickly the XPL+ is to respond to changing measurements.
Slower Measurement Response improves stability and reliability.
values: 1 = slow (0.1 m/min)
2 = medium (1 m/min)
3 = fast (10 m/min)
4 = surge (1.7 m/sec)
5 = turbo (17 m/sec)
APPLICATION PARAMETERS
TECHNICAL REFERENCE
"Surge" and "turbo" are intended for
equipment position monitoring. Use
with caution for level measurement.
See
Measurement Response
TECHNICAL REFERENCE
QUICK START PARAMETERS
PL-532 25