P004 TRANSDUCER
Enter the type of transducer connected to the XPL+ for the Point Number displayed.
ULTRASONIC ULTRASONIC / TEMPERATURE
values: 0 = not entered 100 = ST-H 106 = XPS-40
1 = ST-25 101 = XCT-8 107 = XLT-30
2 = ST-50 102 = XPS-10 108 = XLT-60
3 = ST-100 103 = XCT-12 109 = XLS-30
4 = LR-21 104 = XPS-15 110 = XLS-60
5 = LR-13 105 = XPS-30 111 = XKS-6
112 = XRS-5
P005 (G) UNITS
Enter the units of measure desired for programming Empty (P006) and Span (P007).
values: 1 = metres (m) ( preset )
2 = centimetres (cm)
3 = millimetres (mm)
4 = feet (ft)
5 = inches (in)
P006 EMPT
Enter the maximum distance ( transducer face to vessel bottom ) to be measured, in Units.
This value is preset to 8.000 m ( or equivalent Units programmed ).
The value entered automatically sets Span (P007) to the maximum recommended value.
values: 0.000 to 9999
P007 SPAN
Enter the maximum surface distance from Empty (P006).
Span is automatically preset to 1.1 x the blanking value (P800) less than the Empty
value (P006), unless it is altered manually.
For "distance" Operation (P001 = 3), Span is preset to the Empty value (P006).
Enter a lower value if desired. If the automatic setting is not high enough, see .
Always prevent the monitoried surface from entering the blanking zone.
values: 0.000 to 9999
With the Quick Start Parameters altered as required, proceed to
to identify / verify basic system performance.
1999-06-14
INSTALLATION
OPERATION
PL-532 26