P840 SHORT SHOT NUMBER
Enter the number of short shots to be fired ( and results averaged ) per transmit pulse.
values: 0 to 100
P841 LONG SHOT NUMBER
Enter the number of long shots to be fired ( and results averaged ) per transmit pulse.
This value is automatically altered when Measurement Response ( P003 ) is altered.
( See TECHNICAL REFERENCE Measurement Response ).
values: 0 to 200
P842 SHORT SHOT FREQUENCY
Use this feature to adjust the short shot transmit pulse frequency ( in kHz ).
This feature is automatically altered when Transducer ( P004 ) is altered.
values: 10.00 to 60.00
P843 LONG SHOT FREQUENCY
Use this feature to adjust the long shot transmit pulse frequency ( in kHz ).
This feature is automatically altered when Transducer ( P004 ) is altered.
values: 10.00 to 60.00
P844 SHORT SHOT WIDTH
Use this feature to adjust the width ( in ms ) of the short shot transmit pulse.
This feature is automatically altered when Transducer ( P004 ) is altered.
values: 0.000 to 5.000
P845 LONG SHOT WIDTH
Use this feature to adjust the width ( in ms ) of the long shot transmit pulse.
This feature is automatically altered when Transducer ( P004 ) is altered.
values: 0.000 to 5.000
TECHNICAL REFERENCE