P850 SHORT SHOT BIAS
Use this feature to slant the echo evaluation in favour of the short shot echo when both
short and long shots are evaluated ( see Shot Mode, P803 ). This feature is preset to 20.
values: 0 to 100
P851 SHORT SHOT FLOOR
Enter the minimum echo strength ( in dB above 1 µV ), derived from a short shot, to be
considered for evaluation. This feature is preset to 50.
values: 0 to 100
P852 SHORT SHOT RANGE
Enter the maximum distance in Units ( P005 ) to be measured using short shot echoes.
This feature is automatically altered when Transducer ( P004 ) is altered.
values: 0.000 to 9999