EasyManua.ls Logo

Mircom FA-200 Series - Table 4: Configuration DIP Switch Functions on DM-204 Module

Mircom FA-200 Series
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FA-200 Series Installation and Operation Manual
31
Table 4: Configuration DIP Switch Functions on DM-204 Module
When configuring the DM-204, keep in mind the following information:
Only Indicating Circuit #4 may be configured for visual devices.
If Initiating Circuit #7 is configured as waterflow, the corresponding verified selection becomes a retard
selection.
If Initiating Circuit #8 is configured as alarm, the corresponding latching selection has no effect.
If Initiating Circuit #8 is configured as supervisory, the corresponding verified selection has no effect.
The selection of Class A/B (Style Z/Y) indicating circuits is only a matter of how they are wired. See connection
information on page 15.
If Class A (Style D) initiating circuits are selected the appropriate board jumpers must also be set. Class B
initiating circuits 5 and 6 combine to create Class A Circuit #3, and Class B initiating circuits 7 and 8 combine to
create Class A Circuit #4. DIP switches for circuits 5 to 8 are ignored, and led indicators for circuits 5 to 8 are
non-functional.
Function
DIP Switch
on DM-204
Module
Switch “Off” Switch “On”
Indicating Circuit #3
Audible Device (Bell)
Only
Switch 6, #1 Silenceable Non-Silenceable
Indicating Circuit #4
Audible or Visual
Device
Switch 6, #2 Silenceable Non-Silenceable
Switch 6, #3 Audible Device (Bell) Visual Device (Strobe)
Not Used Switch 6, #4 ----------------- -----------------
Initiating Circuit #5
Alarm Only
Switch 5, #1 Normal Alarm Verified Alarm
Initiating Circuit #6
Alarm Only
Switch 5, #2 Normal Alarm Verified Alarm
Initiating Circuit #7
Alarm or Waterflow
Switch 5, #3 Normal
Verified Alarm / Retarded
Waterflow
Switch 5, #4 Alarm Waterflow
Initiating Circuit #8
Alarm or Supervisory
Switch 5, #5 Normal
Verified Alarm (no effect
on Supv.)
Switch 5, #6 Alarm Supervisory
Switch 5, #7
Non-Latching
Supervisory
(No effect on Alarm)
Latching Supervisory
(No effect on Alarm)
Not Used Switch 5, #8 ----------------- -----------------
Notes:
After you change any configuration switches, perform a system reset.
Do not use retard operation with any external retarding device; maximum retard may not exceed 120
seconds.

Table of Contents

Related product manuals