EasyManua.ls Logo

Mircom FA-200 Series - Appendix D: Power Supply & Battery Calculations

Mircom FA-200 Series
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FA-200 Series Installation and Operation Manual
41
Appendix D: Power Supply & Battery Calculations
Use the form below to determine the required main chassis and secondary power supply (batteries).
Total Current Requirement
ALARM (B)______ Amps.
Battery Capacity Requirement
([STANDBY (A) ______ ] X [(24 or 60 Hours) ___ ]) + ([ALARM (B) ______ ] X [
Alarm in Hr.] _____) = (C) ______AH
* Assuming three initiating circuits in alarm.
Use 0.084 for five minutes of alarm or 0.5 for thirty minutes of alarm as a multiplier figure.
Using the MIR-425/U 2-wire smoke detector. See Appendix A on page 33 for other available smoke detectors.
Total Alarm Current
Must be 2.75 amperes or less for FA-201, FA-202, and FA-204. Indicating Circuits not to exceed 2.4 amperes.
Must be 6 amperes or less for FA-204E. Indicating Circuits not to exceed 5 amperes.
Battery Selection
Multiply (C) by 1.20 to derate battery.
Use BA-1065(6.5AH) Batteries for the FA-201, FA-202, and FA-204 which charges up to 12 AH Batteries.
Use BA-110(10AH) Batteries for the FA-204E.
The FA-204E will charge up to 24AH batteries if they are in an external Mircom BC-160 Battery Cabinet.
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated
continuous power without provision of any disconnect devices. Use #12 AWG wire with 600-volt
insulation and proper over-current circuit protection that complies with the local codes. Refer to
Appendix C on page 38 for specifications.
Power Requirements (All currents are in amperes)
Model
Number
Description
Qt
y
Standby
Total
Standby
Alarm
Total
Alarm
FA-201, FA-
202, FA-204,
FA-204E
Fire Alarm
Control Panel
X 0.110 = 0.220 =
DM-204
Zone Adder
Module
X 0.045 = 0.120 =
RM-204/RM-
208
Relay Module X 0.005 = 0.160 =
PR-100
Polarity Reversal
and City Tie
Module
0.035 = 0.300 =
DACT-100A
DACT/Dialler
Module
0.045 = 0.120 =
RAM-208
Remote
Annunciator
0.035 = 0.090 =
RTI-1
Remote Trouble
Indicator
0.035 = 0.035 =
Two-Wire Smoke Detectors
0.0001
= * 0.090 = 0.090
Four-Wire Smoke Detectors X = =
Signal Load (bells, horns,
strobes, and etc.)
=
Auxiliary Power Supply for Remote Annunciators Alarm =
Total currents (Add above currents) STANDBY (A)(B)

Table of Contents

Related product manuals