Appendix H: Label Requirements for Zone Identification
19.0 Appendix H: Label Requirements for Zone
Identification
For individual zones, the labelling of these zones must be in accordance with ULC/CAN S527-11 Table 2; of
which is partially included below:
LABEL DESIGNATIONS IN ENGLISH DESCRIPTION OF FUNCTION
XXX
a Alarm Signal Activation or
XXX
aAlarm Signal ON
Circuit Or Area Evacuation Manual
Control
XXX
a Alert Signal Activation or
XXX
a Alert Signal ON
Circuit Or Area Alert Manual Control
XXX
a By-pass Ancillary Bypass
XXX
a ON Ancillary Device Indication
XXX
a OFF Ancillary Device Indication
Building Safety or Bldg Safety Common Indication Associated With
Property And Building Safety
XXX
b Specific Indication Associated With
Property And Building Safety
Emergency and building events Common Indication Associated With
Emergency And Building Events
XXX
b Specific Indication Associated With
Emergency And Building Events
XXX
b Emergency Or Building Event Manual
Control
XXX
a Bypass Bypass Output Function
Activate XXX
a or equivalent followed
by
XXX
a
Initiate Manual Control Function
Remote Connection Bypass or
equivalent
Bypass Connection For Fire Service
Response
Signal Circuit Trouble Signal Circuit Fault Indication
Signal Silence Inhibit Prevent Silence Of Signal For A Preset
Time
Supervisory Common Indication Associated With
Supervisory Inputs
XXX
a Specific Indication Associated With
Supervisory Input
Supervisory Signal Silence Manual Signal Silence Control For
Supervisory Signal
Trouble Common Trouble Signal Indicator
XXX
a Trouble Specific, Circuit Or Area Trouble
Signal Indicator
a replace XXX with location and/or device specific description.
b such as alarms, life safety, supervisory, building safety and trouble

Table of Contents

Other manuals for Mircom FX-2000 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FX-2000 series and is the answer not in the manual?

Mircom FX-2000 series Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
NetworkOptional
CommunicationRS-232, RS-485
ProgrammingVia keypad or PC
SLC Loops1
NAC Outputs4
Communication (Additional)Optional Ethernet
Input Voltage120 VAC or 240 VAC, 50/60 Hz
Battery Charging Current1.5 A
Auxiliary Power Output24 VDC
Operating Temperature0°C to 49°C (32°F to 120°F)
Relative HumidityUp to 93% non-condensing