3 Description of functions
3-82
3.6.2. Supported version
CR800-R
A1d or later
CR75x-Q and CR75x-D are not supported
Computer support
Version Remarks
3.6.3. Specifications
The communication specifications of CC-Link IE Field Network Basic are described below.
3.6.3.1. Communication specifications
The communication specifications of the robot are as follows.
192.168.0.20 (initial value, set with NETIP parameters)
Number of occupied stations
Up to four slave stations
Standard Ethernet cable, category 5e or higher (STP cable)
Maximum
number of link
Remote input, RX (*1) Number of occupied stations×64 points
Number of occupied stations×64 points
Remote register, RWr (*3)
Number of occupied stations×32 points
Remote register, RWw (*4)
Number of occupied stations×32 points
(*1) Remote input, RX: Information input from slave to master through bitwise operations.
(*2) Remote output, RY: Information output from master to slave through bitwise operations.
(*3) Remote register, RWr: Information input from slave to master through 16-bit (1 word) operations.
(*4) Remote register, RWw: Information output from master to slave through 16-bit (1 word) operations.