3  Description of functions 
3-33 
 
3.4.7. Parameters 
Table 3-9 Parameter 
Parameter 
Details explanation  Factory setting 
Ethernet 
real-time 
monitor 
MONMODE  Integer 1 
Switch to enable or disable real-time monitoring 
function 
0: Disable 
1: Enable 
1 
MONPORT  Integer 2 
Specify the receive port number and the send port 
number of real-time monitor function.   
(0 to 65535) 
 
First element: Receive port number 
Second element: Send port number 
 
Second element: 
0 is special value, reply to the sender port number 
that is set to UDP header information in the packet 
data start the robot controller has received 
12000, 0 
 
3.4.8. Error 
Table 3-10 Error 
Error number  Error cause and measures 
L.7810 
Error 
NETPORT/MONPORT parameter error 
Cause  The element of NETPORT(1) and MONPORT(1/2) overlap. 
Measures  Please set not to overlap to another port number. 
Detail 
UDP port  number to be used for  real-time  monitoring function  and  real-time 
external  control  is duplicated.  That you cannot  use  the same  port  number, 
please change to a different port number.