3 Description of functions
3-27
3.4.3.2. CR75n series
Example of conditions
IP address of Robot controller
192.168.0.20 (D type Robot controller)
Port number for Real-time monitor
12000, 12001 Receive port = 12000 , Send port = 12001
(1) Connecting the controller and personal computer
Connect the Ethernet cable to the connector of the controller. When the hub is used, use the straight cable. Or when the
personal computer and controller are connected to each other one to one, use the cross cable.
PLC, PC, …
Ethernet communication device
Controller
CR75x-Q / CR75x-D
10BASE-T/100BASE-TX
Ethernet
Cable
(2) Setting the controller parameters
Set the parameters of the robot controller as shown in Table. For more information about parameters, see 3.4.7.
Parameter setting example
NETIP
before
192.168.0.20 (D type Robot controller)
192.168.100.1 (Q type Robot controller)
Same as above (Default value)
MONMODE
MONPORT
12000, 12001* Only when a change is required
(3) Setting the personal computer
To suit your network, please perform the communication settings. Please specify the UDP protocol of Ethernet
communication.
Set the same inbound port number for the Ethernet communication device to receive data as the value of the second
element of the MONPORT parameter set on the robot controller.