3 Description of functions
3-47
3.5.7.2. Device (Device Access)
The following section describes commands used to perform device reading and writing.
3.5.7.2.1. Data Used in Commands
Device code
Access destination devices are specified in request data with the following device codes.
For subcommands 0001 and 0000, specify the device code enclosed in parentheses ( ).
Device Category
Device code
Device No. range Remarks
ASCII
code *1
Binary
code
Special relay
(SM)
Bit
SM**
(SM)
0091H
(91H)
SM0 to
SM4095
Decimal
Special register
(SD)
Word
SD**
(SD)
00A9H
(A9H)
SD0 to
SD4095
Decimal
Input (X)
Bit
X***
(X*)
009CH
(9CH)
R type:
X0 to XFFF
D type:
X0 to X1FFF
Hexadecimal
Output (Y)
Y***
(Y*)
009DH
(9DH)
R type:
Y0 to YFFF
D type:
Y0 to Y1FFF
Hexadecimal
Internal relay
(M)
M***
(M*)
0090H
(90H)
M0 to M18431
Decimal
Cannot be specified with D
type.
Data register (D)
Word
D***
(D*)
00A8H
(A8H)
D0 to D5119
Decimal
CPU buffer
memory access
device
See section 3.5.7.2.6 of this manual.
Cannot be specified with D
type.
*1: When performing data communication in ASCII code, specify device codes with 4 digits for subcommands 003 and
002. For device codes with 3 digits or less, add an asterisk (*) (ASCII code: 2AH) or a space (ASCII code: 20H) after
the device code.
Specify device codes with 2 digits for subcommands 001 and 000. For device codes with 1 digit, add an asterisk
(*) (ASCII code: 2AH) or a space (ASCII code: 20H) after the device code.