8 The Operation of GX Works2
8.3 Time Setting
92
FX3U-ENET-ADP User's Manual
8.3 Time Setting
On the "Time Setting" screen, set the SNTP server IP address and others.
Click the [Time Setting] button on the "Ethernet Adapter" screen to display the screen below.
*1. Set the SNTP server IP address after consulting a network administrator.
*2. Only either one can be selected between "Execution Interval" and "Execution Time".
Setting Description
SNTP Function Setting Select whether to use the time setting function.
SNTP Server IP Address
*1
SNTP Server IP Address is setting.
[Setting range]
0.0.0.1 to 223.255.255.254 (Decimal)
00.00.00.01 to DF.FF.FF.FE (Hexadecimal)
Input Format
Select the input format used to set the SNTP server IP address.
[Setting]
•Decimal
Hexadecimal
Time Zone
Specify the time zone for synchronizing the time.
[Setting]
GMT-12:00, GMT-11:00, GMT-10:00, GMT-9:00, GMT-8:00, GMT-7:00, GMT-6:00, GMT-5:00,
GMT-4:00, GMT-3:30, GMT-3:00, GMT-2:00, GMT-1:00, GMT, GMT+1:00, GMT+2:00, GMT+3:00,
GMT+3:30, GMT+4:00, GMT+4:30, GMT+5:00, GMT+5:30, GMT+5:45, GMT+6:00, GMT+6:30,
GMT+7:00, GMT+8:00, GMT+9:00, GMT+9:30, GMT+10:00, GMT+11:00, GMT+12:00,
GMT+13:00
Execute time setting at turn ON Set whether or not time setting is executed when the power of the PLC main unit is turned ON.
On-error Action
Set whether processing is continued or stopped if an error occurs in the time setting executed when
the power of the PLC main unit is turned ON.
Execution Interval
*2
Specify the time interval (1 to 1440 min) to execute time setting.
Execution Time
*2
Specify the time (in increments of 30 minutes) to execute time setting.