8 The Operation of GX Works2
8.2 Open Setting
90
FX3U-ENET-ADP User's Manual
8.2 Open Setting
On the "Ethernet Adapter Open Setting" screen, set the protocol, open system and others.
Up to four connections can be set up.
MELSOFT connection + MC protocol <= 4 connection
Click the [Open Setting] button on the "Ethernet Adapter" screen to display the screen below.
Setting Description
Protocol
Specify a protocol to be used.
[Setting]
Not Set (The "Open System" and "Host Station Port No." columns are displayed in gray.)
•TCP
•UDP
Open System
Select the open system.
[Setting]
TCP: Select "MELSOFT Connection" or "MC Protocol".
UDP: The open system is fixed to "MC Protocol" (displayed in gray).
Host Station Port No.
Set host station port No.
(This column is valid only when the selected open system is "MC Protocol".)
[Setting range]
MC protocol: 1025 to 5548 or 5560 to 65534
Destination IP Address
Set destination IP address.
(This column is valid only when the selected protocol is "UDP" and the selected open system is "MC
Protocol".)
When this column is valid, "No Setting" is displayed in red.
Click "No Setting" to display the IP address setting dialog which allows setting of the IP address.
When setting of the IP address is completed, the entered IP address is displayed in blue.
[Setting range]
0.0.0.1 to 255.255.255.254 (decimal)
Destination Port No.
Set destination port No.
(This column is valid only when the selected protocol is "UDP" and the selected open system is "MC
Protocol".)
[Setting range]
1025 to 65534