146
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
4 Devices in Detail
4.10 Extension Register [R] and Extension File Register [ER]
•In FX3G PLCs
Data can be written to the memory cassette (EEPROM) up to 10,000 times, and to the built-in memory
(EEPROM) up to 20,000 times.
Every time the RWER (FNC294) instruction is executed, it is counted as a write to the memory. Make sure
not to exceed the allowable number of writes.
When a continuous operation type instruction is used, data is written to the memory in every operation
cycle of the PLC. For preventing this, make sure to use a pulse operation type instruction.
Execution of the LOADR (FNC290)instruction is not counted as a write to the memory.
4.10.8 Registration of data in extension registers and extension file registers
This subsection explains the operating procedures of GX Developer (Ver.8.72A or later).
For details on GX Developer operating procedures, refer to the GX Developer manual.
1 Starting up GX Developer (GPPW)
Click [Start]-[All Programs]-[MELSOFT Application]-[GX Developer] in Microsoft Windows.
2 Setting the PLC model
Set the PLC Series and PLC type as shown below.
*1. For Ver. 8.13P to 8.24A of GX Developer, the PLC type is FX3UC.
Essential set item Contents of setting
PLC series FXCPU
PLC Type
FX3U(C)
*1
, FX3G
*1

Table of Contents

Related product manuals