EasyManua.ls Logo

Mitsubishi Electric MELSEC FX3U - Appendix B-1 Basic Instruction Execution Time; Appendix B: Instruction Execution Time

Mitsubishi Electric MELSEC FX3U
1000 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
961
FX3G/FX3U/FX3UC Series Programmable Controllers
Programming Manual - Basic & Applied Instruction Edition
B Instruction Execution Time
B-1 Basic Instruction Execution Time
31
FNC275-FNC279
Data
Transfer 3
32
FNC280-FNC289
High Speed
Processing 2
33
FNC290-FNC299
Extension File
Register
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
Appendix B: Instruction Execution Time
The instruction execution time in FX3G, FX3U and FX3UC PLCs is as shown below:
Measurement condition
High speed counters and interrupt instructions (I) are not used together.
In operands, data registers are used as target devices.
Indexing (V or Z) is not provided.
Appendix B-1 Basic Instruction Execution Time
•FX3U/FX3UC PLCs
Instruction
Execution time in ON status (µs) Execution time in OFF status (µs)
Remarks
16-bit instruction 32-bit instruction 16-bit instruction 32-bit instruction
Contact instructions
LD 0.065
0.129 µs in 2-step instruction
*1
0.193 µs in 3-step instruction
*3
LDI 0.065
0.129 µs in 2-step instruction
*1
0.193 µs in 3-step instruction
*3
LDP 7.8
LDF 7.8
AND 0.065
0.129 µs in 2-step instruction
*1
0.193 µs in 3-step instruction
*3
ANI 0.065
0.129 µs in 2-step instruction
*1
0.193 µs in 3-step instruction
*3
ANP 7.5
ANF 7.5
OR 0.065
0.129 µs in 2-step instruction
*1
0.193 µs in 3-step instruction
*3
ORI 0.065
0.129 µs in 2-step instruction
*1
0.193 µs in 3-step instruction
*3
ORP 7.4
ORF 7.4
Connection instructions
ANB 0.065
ORB 0.065
MPS 0.065
MRD 0.065
MPP 0.065
INV 0.065
MEP 3.4
MEF 3.4
Output instructions
OUT Y,M 0.065
0.129 µs in 2-step instruction
*2
0.193 µs in 3-step instruction
*3
OUT S 4.8 4.8
OUT T K 0.71 0.71
T192 to T199, T246 to T511
11.6 µs in execution in ON status
8.2 µs in execution in OFF status

Table of Contents

Related product manuals